Offset Compensation Enhances Three-Phase Power Quality Disturbance
Researchers describe a unified Internet-of-Things platform designed for accurate monitoring and forecasting of three-phase building power systems, including power quality disturbance detection. The low-cost setup pairs an ESP8266 microcontroller with three PZEM-004T measurement modules and dedicated current transformers, capturing voltage, current, active power, total energy, frequency, and power factor. Data is sent via Wi‑Fi for real-time analysis, and the hardware was calibrated against Fluke reference instruments, producing mean measurement errors of 0.355% for voltage and 0.324% for current. A 21-day lab deployment showed stable voltage and frequency and revealed a phase-load imbalance, with L3 averaging 959.38 watts and L2 460.64 watts. Forecasting tests found the Extended Additive Holt-Winters model best for daily average power (MAPE 24.53%) and Double Exponential Smoothing best for cumulative energy (MAPE 4.58%). For disturbance detection, an optimization-based offset compensation method is combined with IEEE 1159-2019 threshold rules.